防雷工程中等電位的安裝要求

發表日期:03月24 2020 文章(zhang)編輯:原(yuan)創(chuang) 瀏覽次數:1941次

    在防(fang)雷工程中,等電(dian)(dian)(dian)位(wei)的(de)設(she)計與施(shi)工非常重要,是(shi)防(fang)雷裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi)不可(ke)或缺的(de)組(zu)成部(bu)分。所謂等電(dian)(dian)(dian)位(wei)連接是(shi)使電(dian)(dian)(dian)氣裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi)各(ge)外露可(ke)導電(dian)(dian)(dian)部(bu)分(如(ru)電(dian)(dian)(dian)氣裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi)外殼等 )和(he)裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi)外可(ke)導電(dian)(dian)(dian)部(bu)分(地下干線、水管(guan)、煤氣管(guan)、空調管(guan)等 )電(dian)(dian)(dian)位(wei)基本相等的(de)一種(zhong)電(dian)(dian)(dian)氣連接。今天,鈞和(he)電(dian)(dian)(dian)子就防(fang)雷工程中等電(dian)(dian)(dian)位(wei)的(de)安裝(zhuang)(zhuang)(zhuang)要求做(zuo)如(ru)下分享:


鈞和電子分享防雷工程中等電位的安裝要求


    一、等電(dian)位連接(jie)的重要作用

等電位(wei)分為總等電位(wei)和局部(bu)等電位(wei)。具體作用如下:

1.總等電位連接

等(deng)電位(wei)連(lian)接是(shi)建筑物內電氣 裝置的一項基本安(an)(an)全(quan)措施。其(qi)作用是(shi)降低接觸(chu)電壓,保障人員(yuan)安(an)(an)全(quan)。總(zong)等(deng)電位(wei)連(lian)接能夠明顯的降低接觸(chu)電壓,是(shi)接地(di)故障保護的基本條件。

2.局部等(deng)電位連接(jie)

總等(deng)電(dian)(dian)(dian)位(wei)(wei)連接雖然能大(da)大(da)降低接觸(chu)電(dian)(dian)(dian)壓,如果(guo)建筑物離電(dian)(dian)(dian)源較(jiao)遠,建筑物內(nei)線路(lu)過長,則(ze)過電(dian)(dian)(dian)流保護(hu)動作(zuo)時間和接觸(chu)電(dian)(dian)(dian)壓都可(ke)能超過規定(ding)限值(zhi)(zhi)。在這種情況下應在局部范(fan)圍內(nei)作(zuo)局部等(deng)電(dian)(dian)(dian)位(wei)(wei)連接,使接觸(chu)電(dian)(dian)(dian)壓降至安全電(dian)(dian)(dian)壓限值(zhi)(zhi)50V以下。

二、防雷工程中(zhong)等電位(wei)連接的要求

1.建筑物等(deng)(deng)電位(wei)連(lian)(lian)接(jie)干(gan)線應(ying)從與(yu)接(jie)地裝置(zhi)有不(bu)少(shao)于2處直接(jie)連(lian)(lian)接(jie)的(de)接(jie)地干(gan)線或(huo)總等(deng)(deng)電位(wei)箱(xiang)引出 ,等(deng)(deng)電位(wei)連(lian)(lian)接(jie)干(gan)線或(huo)局部(bu)等(deng)(deng)電位(wei)箱(xiang)間的(de)連(lian)(lian)接(jie)線形成環(huan)形網(wang)絡 ,并就近與(yu)等(deng)(deng)電位(wei)連(lian)(lian)接(jie)干(gan)線或(huo)局部(bu)等(deng)(deng)電位(wei)箱(xiang)連(lian)(lian)接(jie),支線間不(bu)應(ying)串聯(lian)連(lian)(lian)接(jie);

2.總等電位連接主母線的截面規定不應小于裝置中最大PE線截面的一半,但不小于6mm2。如果是采用銅導線 ,其截面可不超過 25mm2。如果為其他材質的導線 ,其截面應承受與之相當的載流量;

3.連(lian)(lian)接(jie)兩個(ge)外(wai)露可導電(dian)(dian)部(bu)(bu)分(fen)的(de)(de)輔助等電(dian)(dian)位(wei)連(lian)(lian)接(jie)線(xian)(xian) ,其截面(mian)(mian)不小于(yu)接(jie)在兩個(ge)外(wai)露可導電(dian)(dian)部(bu)(bu)分(fen)的(de)(de)較小PE線(xian)(xian)的(de)(de)截面(mian)(mian)。連(lian)(lian)接(jie)裝(zhuang)置外(wai)露導電(dian)(dian)部(bu)(bu)分(fen)與裝(zhuang)置外(wai)可導電(dian)(dian)部(bu)(bu)分(fen)的(de)(de)輔助等電(dian)(dian)位(wei)連(lian)(lian)接(jie)線(xian)(xian),其截面(mian)(mian)不小于(yu)相應 PE線(xian)(xian)截面(mian)(mian)的(de)(de)一半;

4.PE線(xian)、PEN線(xian)和(he)等電位連(lian)接(jie)(jie)(jie)線(xian)以及引至接(jie)(jie)(jie)地裝(zhuang)置的(de)(de)接(jie)(jie)(jie)地干線(xian)等,在(zai)安裝(zhuang)竣工后,均應檢測其導電是否(fou)良(liang)(liang)好(hao),決不(bu)許(xu)有不(bu)良(liang)(liang)的(de)(de)或松(song)動的(de)(de)連(lian)接(jie)(jie)(jie)。在(zai)水表(biao)、煤氣表(biao)處,應作(zuo)跨接(jie)(jie)(jie)線(xian)。管道連(lian)接(jie)(jie)(jie)處,一般不(bu)需跨接(jie)(jie)(jie)線(xian),但若導線(xian)不(bu)良(liang)(liang),則應作(zuo)跨接(jie)(jie)(jie)線(xian);

5.需等(deng)電位連(lian)接(jie)的高級裝(zhuang)修金屬(shu)件或零件,應有(you)專用接(jie)線(xian)螺栓與等(deng)電位連(lian)接(jie)支線(xian)連(lian)接(jie),且有(you)標識(shi),連(lian)接(jie)處螺帽緊固,防松零件齊(qi)全。

在防雷(lei)工(gong)(gong)程重(zhong),等(deng)電(dian)位連接還需要根據(ju)現場的(de)(de)(de)實際情況進(jin)行設計與施工(gong)(gong),最終(zhong)目的(de)(de)(de)要消除由(you)于雷(lei)電(dian)流引起的(de)(de)(de)建筑物內(nei)諸金屬(shu)物體(ti)之間(jian)的(de)(de)(de)電(dian)位差,從而保(bao)護建筑物內(nei)部和外部的(de)(de)(de)防雷(lei)安(an)全(quan),防止觸電(dian)電(dian)壓。

 

 